2-wire transmitter with HART protocol 5337A


Model : PR 5337A
Brand: PR Electronics

Head mounted 2-wire transmitter with HART protocol
RTD input type Pt, Ni, Cu
Thermocouple (TC) input type B, E, J, K, L, N, R, S, T, U
Voltage input range: -800…+800 mV
2 analog inputs and 5 device variables with status available
Selectable HART 5 or HART 7 protocol support
1.5kVAC galvanic isolation
Hardware assessed for use in SIL applications
Ex versions for mounting in hazardous gas and dust area

Share as :

Application

  • Linearized temperature measurement with TC and RTD sensors e.g. Pt100 and Ni100.
  • HART communication and 4…20 mA analog PV output for individual, difference or average temperature measurement of up to two RTD or TC input sensors.
  • Conversion of linear resistance to a standard analog current signal, e.g from valves or Ohmic level sensors.
  • Amplification of bipolar mV signals to standard 4…20 mA current signals.
  • Up to 63 transmitters (HART 7) can be connected in a multidrop communication setup.

Technical characteristics

  • HART protocol revision can be changed by user configuration to either HART 5 or HART 7 protocol.
  • The HART 7 protocol offers:
    ∙ Long Tag numbers of up to 32 characters.
    ∙ Enhanced Burst Mode and Event notification with time stamping.
    ∙ Device variable and status mapping to any dynamic variable PV, SV, TV or QV.
    ∙ Process signal trend measurement with logs and summary data.
    ∙ Automatic event notification with time stamps.
    ∙ Command aggregation for higher communication efficiency.
  • 5337D is designed according to strict safety requirements and is therefore suitable for applications in SIL installations.
  • Continuous check of vital stored data.
  • Meeting the NAMUR NE 21 recommendations, the 5337 HART transmitter ensures top measurement performance in harsh EMC environments. Additionally, the 5337D meets NAMUR NE43 and NE89 recommendations.

Mounting / installation

  • For DIN form B sensor head mounting.
  • Configuration via standard HART communication interfaces or by PR 5909 Loop Link.

Source: PR5337 Official Page